Add to Cart
DA-OC-5G Outdoor Cabinet
Dawnergy’s DA-OC-5G series are modular designed outdoor cabinets for wireless communication equipment. They are featured by flexible configuration, quick assembling and easy expansion.
Features
Applications
Cabinet Specifications
Item | Specifications |
Dimensions (W x D x H) (mm) | 650 x 650 x1500 (including base) |
Voltage Input | AC 230V±10% |
Color | Grey |
IP Rating | IP55 |
IP Code Standard | IEC60529 |
Mounting Option | Floor-mount |
Material | Galvanized steel (single layer) |
Cooling Option | DC48V Fan with thermostat (When the temperature in the cabinet exceeds 40℃, the fan will operate automatically) |
Thermostat | KSD301 |
Door Switch | Deek Robot PS056-01N-200 |
Rack Mount Hole Type | M6 square holes |
Lighting | 48V 3W LED lamps |
Lightning protection | Maximum flow capacity: 40kA, protection level: 1500V, response time: < 25nS |
Environmental Requirements | |
Ambient Temperature | -20℃ ~ 45℃ |
Storage Temperature | -40℃~70℃ |
Internal Relative Humidity of Cabinet | ≤85%(+30℃) |
Storage Humidity | 0~100% |
Atmospheric Pressure | 70~106KPa |
Outdoor Cabinet Standard Package
No. | Name | Unit | Quantity |
1 | Key | piece | 2 |
2 | Square Nut | set | 10 |
3 | Screw | set | 10 |
4 | M12 Expansion Bolt | set | 4 |
5 | Sealing Putty | Kg | 1 |
Embedded Power System
embedded power system is composed of a motor frame, a monitoring module and a rectifier module; The power system has DC power distribution function, power monitoring to provide support for external signal input, communication transfer function and AC-DC detection, contactor control and other functions, the whole machine performance is stable, practicability is strong, can be background software operating system.
Specifications
Rectifier Module | Monitoring Module | Power Distribution | Note |
GPR4830B1 | GPM48R | AC power distribution: Single phase three wire input, total power bipolar AC circuit breaker (50A)
DC power distribution: Battery switch: 100A/1P *1 A power down: 63A/1P *3 Secondary power down: 16A/1P*2 |
Rectifier module (minimum 2, maximum 5) |
Dimension (mm)
GPR4830B1 Rectifier Module Specifications
Item | Unit | Min. | Typical | Max. |
AC input voltage | Vac | 90 | 220 | 290 |
AC input voltage frequency | Hz | 45 | 50 | 65 |
Input power factor | 0.99 | |||
Output voltage range | Vdc | 42 | 54 | 58 |
Output current | A | 0 | 30 | |
Accuracy of output voltage stabilization | ±1% | |||
Peak-peak Vp-p | mV | 200 | ||
Output power | W | 0 | 1600 | |
W | 0 | 800 | ||
Output efficiency | % | 91 | ||
% | 83 | |||
Input overvoltage protection | Vac | 288 | 305 | |
Input overvoltage protection recovery point | Vac | 285 | ||
Input undervoltage protection | Vac | 80 | ||
Input undervoltage protection recovery point | Vac | 90 | ||
Output overvoltage protection point | V | 58.5 | 59 | 61.5 |
Output current limiting protection | A | 32 | 33 | 34 |
Monitoring Module Function
Function | Instructions |
The upper computer remote monitoring function to the monitoring unit | The upper computer can inquire, set and control the system monitoring remotely at any time to realize the function of "three remote" |
Monitoring module to rectifier module management | The monitoring module sends control adjustment command or parameter acquisition command to the module through RS485 communication |
Battery management | Management of "battery low voltage, battery under power, battery floating charge management, temperature compensation" |
Monitor the system output management function | Inspection and control systems |
LED indicator function | Signal indicate |
LCD display | Menu to set, modify |
Battery
Features
Specifications
Normal Voltage (v) | Rated Capacity (Ah) 20hrs/25℃ | Approx. Weight (kg) | Dimension (mm) |
12 | 200 | 54 | 522 (L) x 240 (W) x 230 (H) |